Refrigerant sample kit
Purity and contamination testing to AHRI Standard 700.
- Sample cylinder, rated 400 psi — laboratory property, returned with the sample inside it.
- Sample identification label — goes on the cylinder, not on the box, and stays legible after a day in a van.
- The sampling procedure — the same one published here, so the crew doing the work is not reading it off a phone.
- The sample form — tell us the fluid, the system, the source temperature at sampling, and where the report goes. It comes back in the box.
- Draw from
- Liquid valve
- Target sample
- 350 g
- Fill
- 75–80%
- Evacuate to
- ≤ 50 microns
For low-pressure refrigerant, the source tank may be pressurised through the Vapor valve with dry nitrogen.